Every fall and winter, North Idaho loses power for a few hours or a few days at a time. Ice on the lines, wind through the cedars, a tree across a rural feeder near Sagle or Careywood. Homeowners pull out the generator, and a lot of them hook it up in a way that can burn the house down or fry the generator itself. This isn't rare. It's one of the most common calls we get after a storm, either as an emergency or as a cleanup job once someone realizes what they did.

What the problem actually looks like

The classic version is a generator running in the garage or on the porch, feeding the house through a heavy extension cord run in through a cracked-open window or a dryer vent, plugged into a wall outlet with a homemade double-male "suicide cord." The lights come on. It seems fine. What the homeowner doesn't see is that they've just energized the entire house wiring back through the panel, and out onto the utility line, where a lineman working to restore power can be electrocuted by power coming from a generator a quarter mile away.

Other versions show up more slowly. A generator that runs hot and trips its breaker every hour or two. A furnace blower or well pump that used to run fine but now hums, stalls, or burns out within a season of generator use. A cord that gets warm to the touch, or shows melted insulation at the plug. Sometimes it's a carbon monoxide problem instead of an electrical one, a generator running too close to a window or under a carport that fills the house with fumes overnight.

Why it happens

Backfeeding through a dryer outlet or range outlet happens because it's the fastest way to power a whole house without an electrician. People know it works because it's worked for their neighbor or their dad for years without an obvious problem. The danger isn't visible until it is: a lineman gets hurt, or the generator and the utility feed fight each other and something in the panel or the generator fails.

Overloading is the other big cause. A generator rated for 5,000 or 7,000 watts sounds like a lot until you add up a well pump's starting surge, a furnace blower, a refrigerator, and a couple of space heaters. Motors draw three to five times their running wattage for a second or two on startup. If the generator can't cover that surge, it browns out, and that low, unstable voltage is what cooks pump motors and blower motors over time. It's not one dramatic failure, it's cumulative damage from running equipment on dirty, sagging power.

Wrong cord gauge is a quieter version of the same problem. A 100-foot cord rated for light-duty use, run at high amperage, drops voltage over its length and heats up under the load. Homeowners buy a cord by length and price, not by the amp rating stamped on the jacket, and that's usually the gap.

What we do about it

The fix that actually solves this is a properly installed transfer switch, either manual or automatic, tied into the main panel by a licensed electrician. A transfer switch physically isolates the house wiring from the utility feed the instant you switch to generator power, so there's no path for backfeed. Manual transfer switches run roughly 800 to 1,800 dollars installed depending on panel size and generator type, with automatic standby systems running higher, often 3,000 to 8,000 dollars or more once you include the standby generator itself, a concrete pad, gas or propane line work, and permitting.

Before we size anything, we do a load calculation. That means listing the actual equipment the homeowner wants to run during an outage, not everything in the house, and adding up realistic running and starting watts. A well pump alone can need 1,500 to 2,000 starting watts. This tells us what size generator is actually needed and what a transfer switch panel should include, so the homeowner isn't guessing or buying more generator than the situation calls for.

We also check placement and ventilation. Generators need to run outdoors, away from windows, doors, and soffit vents, generally 20 feet is the guideline manufacturers give, though local conditions and wind direction matter too. And we check the cord and inlet: a proper installation uses a locking inlet box on the outside of the house wired to the transfer switch, not a window crack and a household extension cord.

What it costs to ignore

The cheap version of this problem is a burned-out well pump or furnace blower motor, typically 500 to 1,500 dollars to replace depending on the equipment. The expensive version is a house fire from an overloaded cord or a failed backfeed connection, or a fatality, because backfeeding a de-energized line is exactly how utility workers get killed doing storm restoration. Insurance companies also take a hard look at improper generator hookups after a fire claim, and a homemade backfeed setup is the kind of thing that can complicate or reduce a payout. None of this is scare talk, it's just what these setups are actually capable of doing when they fail.

FAQ

Can I just plug my generator into a dryer outlet if I'm careful?

No. There's no safe way to backfeed through a dryer or range outlet, careful or not. The risk to utility workers and to your own wiring doesn't go away with caution, it goes away with an interlock or transfer switch that physically prevents the two power sources from connecting.

How do I know what size generator I actually need?

Add up the running watts of what you want to power during an outage, then add the highest single starting watt draw on top, usually a well pump or air conditioner compressor. That total, with some margin, is your target generator size. An electrician can do this calculation with you in about 15 to 20 minutes if you're not sure how to read the nameplates. If you're in Sagle, Sandpoint, Coeur d'Alene, or elsewhere in Bonner or Kootenai county and want a transfer switch or a load calculation done right, Sageland Electric handles this kind of work regularly.

Need an electrician in North Idaho?

Family-owned, 5-star rated, and 21 years serving Bonner and Kootenai counties.